Technical Specification: RE-104 Conventional Type Fire Alarm Panel.
Primary Power: 120 – 220VAC , 50 Hz
|
Standby Power: 24V D.C (2 Nos of 12v, 7Ah Sealed Lead acid battery).Quiescent current : 55mA
Common Relays : Type : Form CNo of Relays : 3 Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @125VAC.Power Factor : 1
Charging Circuit: Charging Voltage 28.2V, ±0.5VCharging Current 0.5 A (Max.).
Notification Appliance Circuits: Class B wiring Operating Nominal Voltage
: 24VDC Current for NACs
: 0.6 Amp End-Of-Line Resistor
: 4K7, 1/4 watt
Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage
: 14- 21 VDC
Alarm Current : 15 – 30mA
Short Circuit Current
: 42mA Maximum
Loop resistance
: 50 ohms Maximum
End-Of-Line Resistor
: 4.7K, 1/4watt
Standby Current
: 6.8mA (2.4mA for Detectors)
|